PROJECT QUESTION: Also note that the plan sheet SL5 shows flex running down and up from the j-box but does not call out for flex where the 2-inch rigid metal conduit (is this to be PVC/RMC?) and no request for an expansion joint as it passes from the deck to the pilaster. Is there a need for an expansion joint as the 2-inch passes from the slab to the pilaster?

Question:
Also note that the plan sheet SL5 shows flex running down and up from the j-box but does not call out for flex where the 2-inch rigid metal conduit (is this to be PVC/RMC?) and no request for an expansion joint as it passes from the deck to the pilaster. Is there a need for an expansion joint as the 2-inch passes from the slab to the pilaster?

Response:
The roadway lighting conduit that runs from the deck to each junction box in the pilasters shall be rigid metal conduit as noted on SL5 section on the right and the top left elevation. No, the pilaster and deck panels are connected.