PROJECT QUESTION: On sheet SS3 of SS79, note 2 for the ?TYPICAL SIGN SOCKET DETAIL? says there are supposed to be 2 sockets placed 12 inches apart.

Q: On sheet SS3 of SS79, note 2 for the ?TYPICAL SIGN SOCKET DETAIL? says there are supposed to be 2 sockets placed 12 inches apart. Is this for a spare for future us as indicated in note 6? Also, does the estimate of quantities reflect the extra sign sockets needed in note 2, or is the second socket incidental?

A: Yes, the second sign socket is a spare for future use and the quantities include all the sign sockets needed for the project. The second spare sign socket is not incidental.